Levelflex FMP56, FMP57 FOUNDATION Fieldbus Commissioning (block-based operation)
Endress+Hauser 57
Parameter Factory setting for devices with 1 current
output
Factory setting for devices with 2 current
outputs
Value 3 display Current output 1 Current output 1
Value 4 display None Current output 21
The on-site display can be adjusted in the DISPLAY (TRDDISP) transducer block.
11.6 Configuration management
After commissioning, you can save the current device configuration, copy it to another
measuring point or restore the previous device configuration. You can do so using the
Configuration management parameter and its options.
Navigation path in the operating menu
Setup → Advanced setup → Conf.backup disp → Config. managem.
Block operation
Block: DISPLAY (TRDDISP)
Parameter: Configuration management (configuration_management)
Functions of the parameter options
Options Description
33097: Execute backup A backup copy of the current device configuration in the HistoROM is saved to the
display module of the device. The backup copy comprises the transmitter data of the
device.
33057: Restore The last backup copy of the device configuration is copied from the display module to the
HistoROM of the device. The backup copy comprises the transmitter data of the device.
33838: Duplicate The transmitter configuration from another device is duplicated to the device using the
display module.
265: Compare The device configuration saved in the display module is compared to the current device
configuration of the HistoROM.
32848: Clear backup data The backup copy of the device configuration is deleted from the display module of the
device.
HistoROM
A HistoROM is a "non-volatile" device memory in the form of an EEPROM.
While this action is in progress, the configuration cannot be edited via the local display
and a message on the processing status appears on the display.
For devices with FOUNDATION Fieldbus communication, the PD Tag parameter is also
transmitted when duplicating the parameter configuration. If required change PD Tag to
the required value after duplicating the set.