Operating menu Levelflex FMP56, FMP57 FOUNDATION Fieldbus
140 Endress+Hauser
Signal quality
Navigation  Setup → Signal quality
Description Displays the signal quality of the evaluated echo.
Additional information Meaning of the display options
Strong
The evaluated echo exceeds the threshold by at least 10 mV.
Medium
The evaluated echo exceeds the threshold by at least 5 mV.
Weak
The evaluated echo exceeds the threshold by less than 5 mV.
No signal
The device does not find a usable echo.
The signal quality indicated in this parameter always refers to the currently evaluated
echo: either the level/interface echo
4)
or the end-of-probe echo. To differentiate between
these two, the quality of the end-of-probe echo is always displayed in brackets.
In case of a lost echo (Signal quality = No signal) the device generates the following
error message:
F941, for Output echo lost (→  163) = Alarm.
S941, if another option has been selected in Output echo lost (→  163).
Confirm distance
Navigation Setup → Confirm distance
Description Specify, whether the measured distance matches the real distance.
Depending on the selection the device automatically sets the range of mapping.
Selection Manual map
Distance ok
Distance unknown
Distance too small
*
Distance too big
*
Tank empty
Delete map
Factory setting Distance unknown
4) Of these two echos the one with the lower quality is indicated.