Electrical connection Liquiline CM442/CM444/CM448
22 Endress+Hauser
1 2
3
4
5
 24 Protective ground or grounding
connection
1 Protective ground of power unit
2 Serrated washer and nut
3 Protective ground / ground cable, provided by customer
(min. 0.75 mm
2
( 18 AWG))
1)
4 Serrated washer and nut
5 Mounting bolts
1) For a fuse with a rating of 10 A. For a fuse with a rating of 16 A, the protective ground / ground cable must have
a cross-sectional area of at least 1.5 mm
2
( 14 AWG).
NOTICE
Protective ground/ground cable with end sleeve or open cable lug
The cable can become loose. Loss of the protective function!
To connect the protective ground or ground cable to the threaded bolt, only use a cable
with a closed cable lug as per DIN 46211, 46225, form A.
Never connect the protective ground or ground cable to the threaded bolt with an end
sleeve or an open cable lug!