Liquiphant FTL31 IO-Link System integration
Endress+Hauser 23
IO-Link Level 1 Level 2
Switchback delay time, Output 2 (dR2)
Output 2 (OU2)
System Operating hours
μC-Temperature
Unit changeover (UNI) - μC-Temperature
Minimum µC-Temperature
Maximum µC-Temperature
Reset µC-Temperatures [button]
Standard Command
DeviceAccessLocks.DataStorage
Observation Forkfrequency
Switch State Output 1 (OU1)
Switch State Output 2 (OU2)
9 System integration
9.1 Process data
The FTL3x devices can be configured with one or two switch outputs. The status of the switch
output is transmitted in the form of process data via IO-Link.
• In the SIO mode, switch output 1 is switched at pin 4 on the M12 plug. In the IO-Link
communication mode, this pin is reserved exclusively for communication.
• The device's process data are transmitted cyclically in 16-bit chunks.
Bit 0 (LSB) 1 ... 12 13 14 15 (MSB)
Measuring device Fork frequency [0 to 100.0 %], resolution 0.1 % OU1 OU2
lsb: least significant bit
msb: most significant bit
Bit 14 and bit 15 indicate the status of the switch outputs.
Here, 1 or 24 V
DC
corresponds to the logical "closed" state on the switch output.