System integration Liquiphant FTL31 IO-Link
24 Endress+Hauser
The remaining 14 bits contain the value for the fork frequency [0 to 100 %]. A conversion is
not necessary.
Bit Process value Value range
15 OU2 0 = open
1 = closed
14 OU1 0 = open
1 = closed
0 to 13 Raw value, not coverage [0 to 100] Integer
The fork frequency is provided by the device as int13. The decimal separator must then still be
determined using a gradient.
9.2 Reading out and writing device data (ISDU – Indexed Service
Data Unit)
Device data are always exchanged acyclically and at the request of the IO-Link master. Using
the device data, the following parameter values or device statuses can be read out:
9.2.1 Endress+Hauser-specific device data
Designation
ISDU (dec)
ISDU (hex)
Size (byte)
Data type
Access Default
value
Value range Offset/
gradient
Data
storage
Range
limits
Extended order code
259
0x0103
60
String
r/-
ENP_VERSION
257
0x0101
16
String
r/- 02.03.00
Device Type
256
0x0100
2
Uinteger16
r/- 0x92FD
Forkfrequency
79
0x004F
2
UInt16
r/- 0 to 1300 0 / 0.02 No
Simulation Switch
Output 1 (OU1)
89
0x0059
1
UInt8
r/w 0~off 0 ~ off
1 ~ ou1 = high
2 ~ ou1 = low
0 / 0 No 0..2
Simulation Switch
Output 2 (OU2)
68
0x0044
1
UInt8
r/w 0~off 0 ~ off
1 ~ ou1 = high
2 ~ ou1 = low
0 / 0 No 0..2