Liquiphant FTL31 IO-Link Description of device parameters
Endress+Hauser 41
Note On the metal housing cover (IP69), there is no external
signaling via LEDs.
Options Off
On
The function is deactivated after the device is
restarted.
Factory setting Off
Sensor check
Navigation Diagnosis → Sensor check
Description This parameter is used to test if the measuring point is
functioning correctly.
The sensor must not be covered and must be free of residue.
The device compares the current measured values with the
measured values from the factory adjustment.
IO-Link message Check: Following the test, one of the following messages is
displayed:
Message (0x1814) for sensor check passed
Message C103 (0x1813) for sensor check failed
15.2 Parameter
15.2.1 Application
Active switchpoints
Navigation Parameter → Application → Active switchpoints
Description
Choice between standard (0.7 g/cm
3
, 0.5 g/cm
3
) or
customer-specific, user-definable switch points
Switch-on value Last setting selected prior to switching off device.
Selection Standard
User