Liquiphant FTL51B Electrical connection
Endress+Hauser 35
5.2.10 Connecting the cables
Required tools
Flat-blade screwdriver (0.6 mm x 3.5 mm) for terminals
Suitable tool with width across flats AF24/25 (8 Nm (5.9 lbf ft)) for M20 cable gland
1
2
3
!
ød
3.5
24/25 mm
8.0 Nm
A0018023
 29 Example of coupling with cable entry, electronic insert with terminals
1 M20 coupling (with cable entry), example
2
Maximum conductor cross-section 2.5 mm
2
(AWG 14), ground terminal inside the housing +
terminals on the electronics
3
Maximum conductor cross-section 4.0 mm
2
(AWG 12), ground terminal outside the housing
(example of plastic housing with external protective ground connection (PE))
ød Nickel-plated brass 7 to 10.5 mm (0.28 to 0.41 in)
ød Plastic 5 to 10 mm (0.2 to 0.38 in)
ød Stainless steel 7 to 12 mm (0.28 to 0.47 in)
Pay attention to the following when using the M20 coupling
Following cable entry:
Counter-tighten the coupling
Tighten the union nut of the coupling with a torque of 8 Nm (5.9 lbf ft)
Screw the enclosed coupling into the housing with a torque of 3.75 Nm (2.76 lbf ft)
5.3 Post-connection check
 Is the device or cable undamaged (visual inspection)?
 Do the cables used comply with the requirements?
 Do the mounted cables have adequate strain relief?
 Are the cable glands mounted and firmly tightened?
 Does the supply voltage match the information on the nameplate?
 No reverse polarity, is terminal assignment correct?
 If supply voltage is present, is the green LED lit?