Liquistation CSF48 Electrical connection
Endress+Hauser 47
6.4.5 Bus termination
There are 2 ways to terminate the bus:
1. Internal termination (via DIP switch on module board)
"ON"
"OFF"
 45 DIP switch for internal termination
Using a suitable tool such as a tweezer, move all four DIP switches to the "ON" position.
The internal termination is used.
390 W
220 W
390 W
VP
DGND
B/B' A/A'
 46 Structure of internal termination
2. External termination
Leave the DIP switches on the module board in the "OFF" position (factory setting).
Connect the external termination to terminals 81 and 82 on the front of module 485DP or
485MB for 5-V power supply.
The external termination is used.