Liquistation CSF48 Electrical connection
Endress+Hauser 55
Output signals
2 binary signals > 1 s pulse width or edge
The controller must be opened to connect the output and input signals.
6.8 Hardware settings
Setting the bus address
1. Open the housing.
2. Set the desired bus address via the DIP switches of module 485DP or 485MB.
For PROFIBUS DP, valid bus addresses are anything between 1 and 126, and anything
between 1 and 247 for Modbus. If you configure an invalid address, software addressing
is automatically enabled via the local configuration or via the fieldbus.
A0026776
59 Valid PROFIBUS address
67
A0026777
60 Valid Modbus address
195
A0026778
61
Invalid address 255
1)
1)
Order configuration, software addressing is active, software address configured at the factory: PROFIBUS 126, Modbus
247
For detailed information on "Setting the address via software", see the Operating
Instructions →
6.9 Ensuring the degree of protection
Only the mechanical and electrical connections which are described in these instructions and
which are necessary for the required, designated use, may be carried out on the device
delivered.
‣
Exercise care when carrying out the work.