Commissioning Liquisys M CLM223/253
56 Endress+Hauser
A
B
A
B
A
B
A
B
A
B
1
2
3
4
5
A0025218
 31 Optimization of settings T
n
and K
p
A Actual value
B Time
1 T
n
too small
2 T
n
too large
3 K
p
too large
4 K
p
too small
5 Optimum setting
Actuating signal outputs via contacts (R237 to R2310)
Each control contact outputs a cyclical signal whose intensity corresponds to the
controller's actuating value. A distinction is made according to the type of signal cycle:
Pulse length modulation
The bigger the calculated manipulated variable is, the longer the contact affected
remains picked up. The period T can be set to be between 0.5 and 99 s (field R238).
Outputs with pulse length modulation are used to activate solenoid valves.
Pulse frequency modulation
The bigger the calculated manipulated variable is, the higher the switching frequency of
the contact affected. The maximum switching frequency 1/T can be set to be between 60
and 180 min
-1
(field R239). The on-time t
on
is constant. It depends on the set maximum
frequency and is approx. 0.5 s for 60 min
-1
and approx. 170 ms for 180 min
-1
. 170 ms.
Outputs with pulse frequency modulation are used to activate directly controlled
solenoid dosing pumps.