Operating menu Tankside Monitor NRF81
148 Endress+Hauser
"Digital Xx-x" submenu
• In the operating menu, each digital input or output is designated by the respective
slot of the terminal compartment and two terminals within this slot. A1-2, for
example, denotes terminals 1 and 2 of slot A. The same is valid for slots B, C and D
if they contain a Digital IO module.
• In this document, Xx-x designates any of these submenus. The structure of all these
submenus is the same.
D
E
F
C
B
A
1
1
1
1 3
2
2 4
1
HR
CDI
WP
on
SIM
2
2
3
3
4
4
1
1
2
2
3
3
4
4
5
5
6
6
7
7
8
8
POWER
A
1 2 3 4
A1-2 A3-4
i
C
1
2 3 4 5 6 7
C1-2 C3-4
A0026424
46 Designation of the digital inputs or outputs (examples)
Navigation Setup → Advanced setup → Input/output → Digital Xx-x
Operating mode
Navigation Setup → Advanced setup → Input/output → Digital Xx-x → Operating mode
Description Defines the operating mode of the discrete I/O module.
Selection • Disabled
• Output passive
• Input passive
• Input active
Factory setting Disabled