Tankside Monitor NRF81 Electrical connection
Endress+Hauser 33
6.2 Connecting requirements
6.2.1 Cable specification
Terminals
Terminal Wire cross section
Signal and power supply
Spring terminals (NRF81-xx1...)
Screw terminals (NRF81-xx2...)
0.2 to 2.5 mm
2
(24 to 13 AWG)
Ground terminal in the terminal compartment max. 2.5 mm
2
(13 AWG)
Ground terminal at the housing max. 4 mm
2
(11 AWG)
Power supply line
Standard device cable is sufficient for the power line.
HART communication line
Standard device cable is sufficient if only the analog signal is used.
Shielded cable is recommended if using the HART protocol. Observe the grounding
concept of the plant.
Modbus communication line
Observe the cable conditions from the TIA-485-A, Telecommunications Industry
Association.
Additional conditions: Use shielded cable.
V1 communication line
Two wire (twisted pair) screened or un-screened cable
Resistance in one cable: ≤ 120 Ω
Capacitance between lines: ≤ 0.3 µF