Operating menu Tankside Monitor NRF81
190 Endress+Hauser
Description of parameters
Navigation Setup → Advanced setup → Application → Tank calculation
→ HyTD
HyTD correction value
Navigation Setup → Advanced setup → Application → Tank calculation → HyTD → HyTD
correction value
Description Shows the correction value from the Hydrostatic Tank Deformation.
Additional information
Read access Operator
Write access -
HyTD mode
Navigation Setup → Advanced setup → Application → Tank calculation → HyTD → HyTD mode
Description Activates or deactivates the calculation of the Hydrostatic Tank Deformation.
Selection • No
• Yes
Factory setting No
Additional information
Read access Operator
Write access Maintenance
Starting level
Navigation Setup → Advanced setup → Application → Tank calculation → HyTD → Starting level
Description Defines the starting level for the Hydrostatic Tank Deformation. Levels below this value
are not corrected.
User entry 0 to 5 000 mm
Factory setting 500 mm
Additional information
Read access Operator
Write access Maintenance