Tankside Monitor NRF81 Commissioning
Endress+Hauser 67
9.2.7 Tank calculation: Direct level measurement
If no tank calculation is configured, level and temperature are measured directly.
A0029273
A Direct level measurement (without temperature)
B Direct level and temperature measurement
1 Level transmitter (typically FMR540 or FMR51)
2 Tankside Monitor
3 To inventory management system
4 Temperature transmitter
1. Navigate to: "Setup → Level source" and specify from which device the level is
obtained.
2. If a temperature transmitter is connected:
Navigate to: "Setup → Liquid temp source" and specify from which device the
temperature is obtained.