Brief Operating Instructions
Gammapilot M FMG60
PROFIBUS PA
Radiometric measurement
These Instructions are Brief Operating Instructions; they are
not a substitute for the Operating Instructions pertaining to
the device.
For detailed information, refer to the Operating Instructions
and other documentation.
Available for all device versions via:
Internet: www.endress.com/deviceviewer
Smart phone/Tablet: Endress+Hauser Operations App
KA01093F/00/EN/15.18
71402951
2018-08-13

Questions and Answers

  • S
    Stephen SharpSep 12, 2025
    What does SIL lock device mean on Endress+Hauser PROFIBUS PA Measuring Instruments?
    • C
      Caitlyn GonzalezSep 12, 2025
      If the Endress+Hauser Measuring Instruments display 'SIL lock device', it means that the SIL_locking process has not been completed.
  • J
    John BarberAug 25, 2025
    What to do if full/covered not calibrated on Endress+Hauser Measuring Instruments?
    • C
      charles55Aug 25, 2025
      If Endress+Hauser Measuring Instruments are showing a 'full/covered not calibrated' message, perform a full/covered calibration using the calibration function group.
  • A
    andrewsseanAug 25, 2025
    What to do if empty/free not calibrated on Endress+Hauser Measuring Instruments?
    • J
      Jason RodriguezAug 26, 2025
      If Endress+Hauser Measuring Instruments are showing a 'empty/free not calibrated' message, perform an empty/free calibration using the calibration function group.
  • S
    sampsonchristopherSep 23, 2025
    What to do if Endress+Hauser Measuring Instruments have download error?
    • W
      williamaustinSep 23, 2025
      To resolve a 'Download error' on your Endress+Hauser Measuring Instruments, repeat the download process.
  • J
    joyce21Sep 12, 2025
    What to do if electronics defect on Endress+Hauser PROFIBUS PA?
    • D
      Deborah WhiteSep 12, 2025
      If you are facing an 'electronics defect' error with your Endress+Hauser Measuring Instruments, try switching the instrument off and on.
  • J
    Julia WilsonSep 18, 2025
    How to fix 'Linearization table not defined' on Endress+Hauser PROFIBUS PA Measuring Instruments?
    • M
      Mark MillerSep 18, 2025
      To resolve the 'Linearization table not defined' error on your Endress+Hauser Measuring Instruments, enter or complete the linearization table in the "linearization" (*4) function group. Ensure the table contains the endpoints 0% = 1000 cps (standardized) and 100% = 0 cps (standardized). When entering via FieldCare, select the correct table type (lin. tab. "level" or "concentration").
  • M
    Michael GutierrezSep 5, 2025
    What to do if Endress+Hauser Measuring Instruments show error W153?
    • K
      Kevin ReeseSep 5, 2025
      If your Endress+Hauser Measuring Instruments display error W153, wait for completion of the initializing procedure.
  • M
    moyermitchellSep 6, 2025
    What to do if Endress+Hauser PROFIBUS PA Measuring Instruments show error A106?
    • G
      Gary RodriguezSep 6, 2025
      If your Endress+Hauser Measuring Instruments display error A106, wait for completion of the download.
  • B
    bradleypetersonSep 18, 2025
    How to troubleshoot 'Linearization table not plausible' on Endress+Hauser PROFIBUS PA?
    • J
      Joseph BlackwellSep 18, 2025
      To resolve the 'Linearization table not plausible' error on your Endress+Hauser Measuring Instruments, check the monotony of the linearization table and adjust it if necessary using the "linearization" (*4) function group.
  • K
    katherineharringtonAug 30, 2025
    What happens when Endress+Hauser Measuring Instruments issues a warning error?
    • E
      Eric HoltAug 30, 2025
      When a warning error occurs, the Endress+Hauser Measuring Instruments device continues measurement, and an error message is displayed, alternating with the measured value.

Endress+Hauser PROFIBUS PA Specifications

General IconGeneral
Communication ProtocolPROFIBUS PA
ManufacturerEndress+Hauser
Power supply9-32 V DC (via PROFIBUS PA)
Protection classIP67
Housing materialStainless steel or plastic