Wiring Gammapilot M FMG60 PROFIBUS PA
20 Endress+Hauser
Feature 30 of the ordering information: power supply
wiring/output wiring
Connection compartment
with terminals for
Supply
voltage
Signal
output
A Non-Ex; non-Ex 1 2
1
2
A0018082
B Ex e; Ex ia 1 2
C Ex e; Ex e 1 1
D Ex d (XP); Ex d (XP) 1 1
E Ex d (XP); Ex ia (IS) 1 2
F Dust-Ex; Dust-Ex 1 1
G Ex e, Dust-Ex; Ex e, Dust-Ex 1 1
H Ex d, Dust-Ex; Ex d, Dust-Ex 1 1
J Ex e, Dust-Ex; Ex ia, Dust-Ex 1 2
K Ex d, Dust-Ex; Ex ia, Dust-Ex 1 2
L Dust-Ex; Ex ia 1 2
4.4 PROFIBUS PA cable specifications
Always use a twisted, shielded two-wire cable. Make sure to comply with the following
specifications if installing in hazardous areas (EN 50 020, FISCO model):
Loop-resistance (DC): 15 to 150 Ω/km
Inductance per unit length: 0.4 to 1 mH/km
Capacitance per unit length: 80 to 200 nF/km
The following are examples of suitable cable types:
Non-hazardous area:
Siemens 6XV1 830-5BH10 (gray)
Kerpen CEL-PE/OSCR/PVC/FRLA FB-02YS(ST)YFL (gray)
Belden 3076F (orange)
Hazardous area:
Siemens 6XV1 830-5AH10 (blue)
Belden 3076F
Kerpen CEL-PE/OSCR/PVC/FRLA FB-02YS(ST+C)YFL (blue)