Why parameters cannot be changed in Endress+Hauser Measuring Instruments?
- EEileen PerezAug 14, 2025
Parameters that only show values or settings cannot be changed. Also, the hardware write protection may be enabled; check the WRITE_LOCK parameter in the Resource Block: LOCKED indicates write protection is enabled, while UNLOCKED means it's disabled. The block operating mode might be set incorrectly; some parameters are changeable only in OOS (out of service) or MAN (manual) modes. The entered value could be outside the parameter's specified input range; enter a suitable value or increase the input range if needed. For Transducer Blocks, the programming level might not be enabled; enable it by entering the code in the "Un-/Locking - Access Code" parameter or using the Service Code in the Service parameters.