15Endress+Hauser
Prosonic T - FMU 130, 131, 230, 231, 232
Functional Display
Prosonic T differentiates between the operational faults alarm and warning.
(See also “Information on the measuring point”, page 28.)
2-Wire
If the Prosonic T Identifies an Alarm
the bargraph flashes, if the display is plugged
the current output adopts a preselected value (–10% = 3.8 mA, +110%, HOLD)
an error code is output in V9H0
If the Prosonic T Identifies a Warning
the instrument continues to measure
an error code is output in V9H0
4-Wire
If the Prosonic T Identifies an Alarm
the bargraph flashes, if the display is plugged
the red LED lights up
the current output adopts a preselected value (–10% = 2.4 mA, +110%, HOLD)
an error code is output in V9H0
If the Prosonic T Identifies a Warning
the red LED flashes
the instrument continues
to measure
an error code is
output in V9H0
LED off LED on
Function Green LED Red LED Bar graph in Error Code in
display V9H0?
Caution 2-wire versions: The green LED is not used to display operational status due to power
consumption. There is no red LED.
2-Wire
Entry completed
Error status
– Alarm YES
– Warning YES
4-Wire
Entry completed
Error status
– Alarm YES
– Warning YES