Prosonic T - FMU 130, 131, 230, 231, 232
Endress+Hauser
Operating via the Matrix
The Prosonic T is calibrated and operated using the 10 x 10 Endress+Hauser user
matrix.
The basic configuration can be realized in its simplest form over three matrix fields.
Configuration and operation are always identical for:
• Local push-button operation with display
• Operation via handheld terminal
• Operation via the Silometer FMX 770 (BA 136F) or FXN 671 (TI 236F)
• Operation via a process bus
Local Push-button Operation with Plug-In Display
Display Elements
VH position
Parameter
Bar display:
– Display: current or echo quality
– flashes on alarm
Push Buttons
Push-button Function
Selecting the Matrix Field
Selecting the vertical matrix position.
Selecting the horizontal matrix position.
and The display jumps to V0H0.
Entering Parameters
or Activates the appropriate matrix position. The selected
position flashes.
Changes the value of the flashing position by +1.
Changes the value of the flashing position by –1.
and Resets the value entered to the original value if it is not yet
confirmed with V
or H.
Confirming the Entry
or Confirms the entry by leaving the matrix field.
Locking/Unlocking the Matrix
and Locking matrix, 9999 is shown in V9H9.
and Unlocking matrix, 333 is shown in V9H9.