Function group: SYSTEM UNITS
The following instructions explain in more detail pages 34 and 37.
Instructions for user-defined mass units:
Custom flow unit
or
Custom total unit
Examples:
To display the
mass flow
of superheated steam at 200 °C and 12 bar in kg/h.
According to the steam table the density is 5.91 kg/m
3
:
Custom flow unit =
To display the
totalized mass
in kg for the same superheated steam application (density 5.91 kg/m
3
):
Custom total unit =
5.91
1000
3600
1
1
= 21.276
••
5.91
1000
1
1
= 0.00591
1000
1
Density at operating
conditions in kg/m
3
for desired time base
(not for totalizer)
.../s 1
.../min. 60
.../h 3600
.../d 86400
for desired mass
unit
kg/... 1
t/... 1000
lbs/... 0.4536
ba032y01
Prowirl 77 PROFIBUS-PA 6 Device Functions