26
Room temperature control requires that the unit has
either a temperature sensor (optional extra) connected to
the eAir control panel or a room temperature transmitter
(optional extra) connected to the eAir motherboard.
Indoor air temperature control measurements must be
activated separately from settings.
Heating is active when the control requests heating, i.e.
when the set point temperature value is higher than the
measured extract air (or indoor air) temperature. Cooling
is active when the control requests cooling, i.e. when the
set temperature value is lower than the measured extract
air (or indoor air) temperature. Heating and cooling can be
active at the same time, if the ventilation unit is equipped
with supply air absolute humidity control (optional extra).
W models have a water heating coil return water check
function that activates heating if the temperature of
the return water drops too much. If the return water
temperature is still dropping, the ventilation unit will shut
down and set a freeze protection alarm.
If Max. heating / Max. cooling is selected from the control
panel quick menu, ecient heating or cooling activates
momentarily. The function forces the supply air control
to its limit value and raises the fans to the Manual boost
level.
The function will run until the temperature value set in
the control panel main screen is reached.
Alarms
In alarm modes the ventilation unit either stops
completely (A alarms, such as re alarm) or remains in
malfunction mode, in which the fans operate at minimum
power (the so-called AB alarms, such as if supply air is too
cold).
It is possible to congure the unit so that the fans stop
also in AB-alarm.
Filter guard (optional extra)
The ventilation unit can be tted with a lter guard
function as an optional extra. Filter guard activates a
service reminder alarm if the lter is blocked. The lter
guard function requires that a ventilation unit has
dierential pressure sensors installed. These measure
the dierence in pressure caused by the lters. If the
ventilation unit is ordered from the factory with a lter
guard function, the automation will automatically
activate the lter guard function when the setup wizard is
completed. The fans will work at full power for some time,
during which the system measures the pressure dierence
caused by clean lters, and sets the right value to indicate
blocked lters. The lter guard is active following this. The
service reminder alarm is sent, if the alarm level set by the
automation is exceeded. The lter guard tests the lters
every Wednesday at 12:00. Both fans will operate at full
power for a few minutes.
The lter guard alarm must be manually acknowledged
in the Settings > Alarm > Acknowledge maintenance
notication menu. If the type or manufacturer of the lter
is changed, the alarm limits of the lter guard must be
updated. This is done in the menu: Settings > Alarm >
Update alarm limits for lter guard.