47Installation instructions for professionals
Enervent Svea
PRODUCT INFORMATION ACCORDING TO
EU COMMISSION REGULATION NO 1253/2014 AND 1254/2014
Supplier’s name or trade mark Enervent
Supplier’s model identier Svea
Specic energy consumption (sec) in kWh/(m
2
.A)
• Cold climate
• Average climate
• Warm climate
-76,8
-37,3
-14,6
Declared typology in accordance with article 2 of this regulation RVU / BVU
Type of drive installed or intended to be installed Multi-speed drive
Type of heat recovery system Regenerative
Thermal eciency of heat recovery 84,8
Maximum ow rate in m
3
/h 619
Electric power input of the fan drive, including any motor control equip-
ment, at maximum ow rate (W)
298
Sound power level (L
WA
), rounded to the nearest integer 48
Reference ow rate in m
3
/s 0,12
Reference pressure dierence in Pa 50
SPI in W/(m
3
/h) 0,31
Control factor and control typology in accordance with the relevant
denitions and classication in annex VIII, table 1
0,65
Declared maximum internal and external leakage rates (%) for bidirec-
tional ventilation units
<4% / <0,8%
Position and description of visual lter warning for rvus intended for use
with lters, including text pointing out the importance of regular lter
changes for performance and energy eciency of the unit
Filter warning on control
panel. Instructions in user
manual.
Internet address for disassembly instructions as referred to in point 3
https://doc.enervent.com/out/
out.ViewFolder.php?folderid=957
The annual electricity consumption (AEC) (in kWh electricity/a) 162
The annual heating saved (AHS) (in kWh primary energy/a) for each type
of climate
• Cold climate
• Average climate
• Warm climate
8084
4132
1869
The information on the energy label for this product has been dened with local demand control. Local demand control means that the ventilation unit continuously regulates the fan
speed(s) and ow rates based on more than one sensor. Please remember to connect all local sensors (some sold as extra equipment) in order to achieve the declared energy class.