32
5 Use Home The options are Home or Oce. In Oce mode,
the unit can be switched on only by using a time
program.
Temperature control Supply air
Extract air is the
default setting for
units with cooling
functionality.
Supply air maintains the supply air temperature at
the value specied on the main view. This is the
default setting for units with no cooling functionality.
Room temperature average or Extract air compare
the temperature setting in the main view with the
room temperature or extract air temperature and
heat or cool the supply air accordingly. To be able
to use room temperature control, at least one room
temperature sensor must be connected. These set-
tings are recommended only for units with cooling
functionality.
Cooling OFF Options are ON/OFF.
Outside temperature
limit for cooling
17°C When the outside temperature is below the set
value, no active cooling is allowed.
Heating ON Options are ON/OFF.
Outside temperature
limit for heating
25°C When the outside temperature is above the set
value, no heating is allowed.
Min. supply air
temperature
13°C This is the minimum temperature for the supply air
when the temperature control value is Extract air or
Room temperature average.
Maximum supply air
temperature
40°C This is the maximum temperature for the supply air
when the temperature control value is Extract air or
Room temperature average.
Heating/cooling
limitation
OFF This setting is used if the user wants to prevent
continuous switching between heating or cooling
when the temperature setpoint is very close to the
desired temperature.
Heating 18°C When the extract air (or the room temperature
average, in room temperature mode) temperature
drops, the heating is not activated until this tem-
perature is reached.
Cooling 24°C When the extract air (or the room temperature
average, in room temperature mode) increases, the
cooling is not activated until this temperature is
reached.
TE20-21 sensor OFF Options are ON/OFF. If both sensors are selected
here, the temperature control uses the mean tem-
perature of the room sensors. If you have installed
only one wall mounting bracket with room tem-
perature sensor, it is TE20.
Room temperature
sensor 1-3
OFF Options are ON/OFF. These sensors are room tem-
perature transmitters that are connected to the
ventilation unit. The sensors can be included or left
out of the mean room temperature measuring by
setting them on or o.