AF / DCU MANUAL
IOM-52 22 of 23 Apr 13 R2
REFRIGERATION
SeasonalMaintenance
Checkoperatingtemperatureandpressures.
Theexternalsurfaceoffinnedcoilscanbecleanedusingalowpressurewatersprayandabrush.
Coilfinsareeasilydamaged.Donotusehighpressuresteamorwatertocleancoils;itwill
permanentlydamagethecoil.Whenusingcleaningadditivesorsolutionstheymustbecompatible
withthecoilmaterialsorcoatings.Useafincombtostraightenanydamagedorbentfins.
Inspectrefrigerantlinesforevidenceofoilleaks.
Checkcondenserfansandtightensetscrews.
NOTE:Airflowisrestrictedbydirtycoils,slippingfanbeltsetc.Thiswillreducecapacity.
PressureControls
Encapsulatedpressurecontrolshavefixedsettingsandarenotadjustable.Mostpressurecontrolshave
thesetpointmarkeddirectlyonthecontrol.Thefollowingtableshowstypicalcutinandcutoutsetpoint
usingsaturatedtemperature;refertorefrigerantspecificsaturatedtemperature/pressuretablesto
converttopressure.
TYPICALSETTINGS(SaturatedTemperature)
PressureControls CutIn CutOut
LowPressure 35°F(1.7°C) 15°F(‐9.4°C)
HighPressure Manual 150°F(65.6°C)
HighPressure(WaterCooled) 105°F(40.6°C) 125°F(51.7°C)
CondenserFan
Varioussettingstomaintainsaturatedcondensing
temperaturebetween85°Fto125°F(29.4°Cto51.7°C)
Note:Specializedapplicationsordifferentrefrigerantsmayhavepressurecontrolsettingsoutside
typicalsettings.Referdirectlytomountedpressurecontrols,wiringdiagramand/orunitfunctionfor
specificdetails.
Note:Equipmentwithareceivercanusehighpressurecontrolswiththelowersettingofthanthat
notedabove,themaximumratedworkingpressureofthereceiver,90%ofthepressurereliefvalve
rating.