A
AF / DCU MANUAL
IOM-52 23 of 23 Apr 13 R2
TROUBLESHOOTINGCHART
Symptoms Problem Cure
Highheadpressure DirtyCondenser Cleanorwash
Flattenedorhaildamaged
fins
Combfins
Condenserfanmotorsnot
running
Checkandcorrectproblem
Brokencondenserfanblade Replaceblade
Defectiveorincorrectlyset
condenserfancycling
control
Adjustorreplaceasrequired
Condenserair,short
circuiting
Checktemperatureofinletairandcorrectas
required.Ensureproperairflowclearances.
Systemoverchargedwith
refrigerant
Reclaimexcessrefrigerant
Noncondensableinsystem Reclaimrefrigerant,evacuatesystem,recharge
withnewrefrigerant
Controlrelays
chatterorsolenoid
valvesnot
energized
Voltagedropinfieldwiring
tosolenoidsorthermostat.
(greaterthan10%)
Checkvoltageatsolenoidorrelaywhenitis
energized,Ifitislessthan10%ofratedvoltage,
checkwiresize,ordeterminecauseandrepairas
required.
Primaryvoltagenotwithin
10%ofunitratingplate.
Haveelectriciancheckandrepairasrequired.