Engel MT45F-U1D-P - Trouble Flowchart; Does Not Get Cold

Engel MT45F-U1D-P
24 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
※1 Ambient temp 25℃
※2 Ambient temp 25℃~-16
5. TROUBLE SHOOTING
10
Is the output voltage from the power
supply to the compressor normal?
Approx. AC13V - 18V ※1
Does not get Cold
(Temperature setting -18
)
Is compressor
running?
Lower than AC13V
Checking
Is the special
fuse of the DC
cord or the
blade fuse of
the power
supply blown?
Are wirings and couplers
connected?
Replace the
power supply.
Replace the fuse
See page 13
Check 1
See page 13
Check 2
Test result
Judge
Fixing
Connected repair.
Replace the
power supply.
See page15
Check 7
Power supply is
broken
Normal
Yes
Yes No
Normal
Normal
No
Yes
No
Out of standard
Gas leak, clogging, etc.
Measurement of rated
current of refrigerator or
compressor
Replace the
cooling unit.
See page 15
Check 7
Is temperature
controller (digital
display) lit
?
Is the output voltage from the control
assembly to the power supply normal?
Normal
Abnormal
See page 14
Check 5
teperature controller
is broken.
Replace the
teperature
controller.
Replace the
power supply.
Lower than AC13V
Power supply is
broken
Is the output voltage from the power
supply to the compressor normal?
Approx. AC13V - 18V ※1
See page 13
Check 2
Abnormal
Out of standard
Abnormal
Abnormal
Replace the
cooling unit.
Compressor lock etc.
Measurement of rated
current of refrigerator or
compressor
Compressor resistance
About 1.7Ω (at 25 ℃)
※Using analog tester
∞Ω
Out of standard
Normal
Coil disconnection
Coil short circuit
Is the output voltage from the power
supply to the control assembly normal?
Out of standard
Power supply is
broken
teperature controller
is broken.
Normal
Replace the
teperature
controller.
See page 14
Check 6
Abnormal
Abnormal
Abnormal