EasyManua.ls Logo

Enko CCS 3100 - CCS3100 Phase Voltage Faults; Phase Voltage High Faults; Phase Voltage Low Warnings

Default Icon
40 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
CCS3100
16
User Manual R0.2
S Phase Voltage High Warning (Vs High Warn)
Warning Definition: Indicates that the S Phase Voltage connected to the terminal “24”, which is defined as “S”, is
higher than the value entered to the “P146 Mains Voltage High Warn” parameter. It is just a warning message. Does
not stop the motor.
Possible Causes and required actions: There may be a voltage rise in the system. The value that is entered to the
parameter may have been wrong for the application.
S Phase Voltage High Fault (Vs High Alarm)
Fault Definition: Indicates that the S Phase Voltage connected to the terminal “24”, which is defined as “S”, is higher
than the value entered to the “P145 Mains Voltage High Alarm” parameter. It is a malfunction that stops the
compressor rapidly.
Possible Causes and required actions: There may be a voltage rise in the system. The value that is entered to the
parameter may have been wrong for the application.
T Phase Voltage High Warning (Vt High Warn)
Warning Definition: Indicates that the T Phase Voltage connected to the terminal “23”, which is defined as “T”, is
higher than the value entered to the “P146 Mains Voltage High Warn” parameter. It is just a warning message. Does
not stop the motor.
Possible Causes and required actions: There may be a voltage rise in the system. The value that is entered to the
parameter may have been wrong for the application.
T Phase Voltage High Fault (Vt High Alarm)
Fault Definition: Indicates that the T Phase Voltage connected to the terminal “23”, which is defined as “T”, is higher
than the value entered to the “P145 Mains Voltage High Alarm” parameter. It is a malfunction that stops the
compressor rapidly.
Possible Causes and required actions: There may be a voltage rise in the system. The value that is entered to the
parameter may have been wrong for the application.
R Phase Voltage Low Warning (Vr Low Warn)
Warning Definition: Indicates that the R Phase Voltage connected to the terminal “25”, which is defined as “R”, is
lower than the value entered to theP144 Mains Voltage Low Warn” parameter. It is just a warning message. Does
not stop the motor.