P071: Input Delay 8:
After the relevant input is active, at the end of the time value entered to this parameter, the device takes the input
as active.
P072: Input Contact Type 8:
The contact type of the relevant input, can be selected as NO (normally open) or NC normally closed.
2.2.4 Digital Output Parameters
Functions That Can Be Assigned to Outputs:
The functions that can be assigned to the outputs and their explanations are as follows.
None: No function is assigned to the related digital output. If no connection has been made, it is recommended to
set it as "None".
Main Con.: The output function that the Main Contactor will be connected.
Star Con.: The output function that Star Contactor will be connected.
DeltaCon.: The output function that the delta contactor will be connected.
LoadValve: The output function that the load valve will be connected.
Alarm: In case of any fault, this output becomes active.
Warning: In case of any warning, this output becomes active.
Alarm+Warn: In case of any fault or warning, this output becomes active.
Fan: The output function where the Fan Contactor will be connected.
OnLoad: The output is active when the compressor is running and the solenoid valve is active.
Idle: The output is active when the compressor is running and the solenoid valve is passive.
Running: When the compressor motor is running, this output is active.
Stopping: When the compressor motor stops, this output is active.
Horn: The output to which horn, siren or similar warning equipment will be connected.
Dryer-Time: The output related to the dryer. See “Application note Dryer Functions”.
Dryer-T2: The output related to the dryer. See “Application note Dryer Functions”.
RSS Active: This output is activated only when the starting source is selected as Modbus, Digital input or Modbus +
Digital input.
T.LowAlarm: This output is activated when the screw oil temperature drops below the value entered to the "P124
Temperature 1 Low Alarm " parameter.
T.Up Alarm: This output is activated when the screw oil temperature rises above the value entered to the "P122
Temperature 1 High Alarm " parameter.
T.Low Warn: This output is activated when the screw oil temperature drops below the value entered to the "P125
Temperature 1 Low Warn" parameter.
T.Up Warn: This output is activated when the screw oil temperature exceeds the value entered to the "P123
Temperature 1 High Warning" parameter.