CCS3100
28
User Manual R0.2
P051: Input Delay 3:
After the relevant input is active, at the end of the time value entered to this parameter, the device takes the input
as active.
P052: Input Contact Type 3:
The contact type of the relevant input, can be selected as NO (normally open) or NC normally closed.
P054: Input Function 4:
The Function parameter that will be assigned to the input on the device's terminal 16, which is defined as DI4. See
“Functions That Can Be Assigned to Inputs”, Default function is “PhaseSeq”.
P055: Input Delay 4:
After the relevant input is active, at the end of the time value entered to this parameter, the device takes the input
as active.
P056: Input Contact Type 4:
The contact type of the relevant input, can be selected as NO (normally open) or NC normally closed.
P058: Input Function 5:
The Function parameter that will be assigned to the input on the device's terminal 17, which is defined as DI5. See
“Functions That Can Be Assigned to Inputs”, Default function is “OilPres.”.
P059: Input Delay 5:
After the relevant input is active, at the end of the time value entered to this parameter, the device takes the input
as active.
P060: Input Contact Type 5:
The contact type of the relevant input, can be selected as NO (normally open) or NC normally closed.
P062: Input Function 6:
The Function parameter that will be assigned to the input on the device's terminal 18, which is defined as DI6. See
“Functions That Can Be Assigned to Inputs”, Default function is “Aux1 Alarm”.
P063: Input Delay 6:
After the relevant input is active, at the end of the time value entered to this parameter, the device takes the input
as active.
P064: Input Contact Type 6:
The contact type of the relevant input, can be selected as NO (normally open) or NC normally closed.
P066: Input Function 7:
The Function parameter that will be assigned to the input on the device's terminal 19, which is defined as DI7. See
“Functions That Can Be Assigned to Inputs” Default function “None”.
P067: Input Delay 7:
After the relevant input is active, at the end of the time value entered to this parameter, the device takes the input
as active.
P068: Input Contact Type 7:
The contact type of the relevant input, can be selected as NO (normally open) or NC normally closed.
P070: Input Function 8:
The Function parameter that will be assigned to the input on the device's terminal 20, which is defined as DI8. See
“Functions That Can Be Assigned to Inputs”, Default function is “FThermic”.