33
IQ System Controller 3M quick install guide
Setting up PCS on-site during commissioning
1. Ensure the availability of the following Enphase products as required on-site to implement PCS.
PRODUCT SKU
IQ System Controller 3M SC200D111CMC1US01
IQ Combiner 5/5C X-IQ-AM1-240-5, X-IQ-AM1-240-5C, X-IQ-AM1-240-5-HDK, X-IQ-AM1-240-5C-HDK
IQ Battery 5P IQBATTERY-5P-1P-NA
Microinverters IQ8 Series
IQ Meter Collar MC200011V01
2. Installation of the CTs
The current transformer (CT) placement for each of the features is shown in the following table:
ENPHASE POWER CONTROL FEATURE CURRENT TRANSFORMERS UTILIZED CT PLACEMENT
Main Panel Upgrade
(MPU) avoidance
Production CT, Battery
CT, and IQ Meter Collar
Production CT is placed inside the IQ Combiner.
IQ Meter Collar is placed in the meter socket between
the main panel busbar and utility meter.
Battery CT is to be placed inside the IQ System Controller.
IQ Battery oversubscription Battery CT1 Battery CT is to be placed inside the IQ System Controller.
1
Battery import only
Production CT and
IQ Meter Collar
Production CT is placed inside the IQ Combiner.
IQ Meter Collar is placed in the meter socket between
the main panel busbar and utility meter.
Battery export only
Production CT, Battery
CT, and IQ Meter Collar
Production CT is placed inside the IQ Combiner.
IQ Meter Collar is placed in the meter socket between
the main panel busbar and utility meter.
Battery CT is to be placed inside the IQ System Controller.
Aggregate power export limit IQ Meter Collar
IQ Meter Collar is placed in the meter socket between
the main panel busbar and utility meter.
1
Battery CT is not utilized for IQ Battery oversubscription, but it is required for other functionality of IQ Battery 5P.
NOTE: Refer to the CT Wiring section for details.
3. Ensure all PCS-controlled busbars and/or conductors are protected with suitably rated overcurrent devices that are appropriately sized
for the busbar rating or conductor ampacity.
4. For sites with main panel upgrade (MPU) avoidance mode enabled, indicate this with the label.
Record the maximum operating current value on the label.
The label is provided as part of the IQ System Controller Literature kit.
MPU avoidance label
01 INITIAL RELEASE - ECO-00
21 MAY 24
M. Nagy
17 FEB 21
780-00569
1 1
Label, Enpower, PCS, Field
01
D
C
B
A
B
A
1
3
45
678
12
34
56
78
1420 N. McDowell Blvd.
PETALUMA, CA 94954
(707) 763-4784
The information contained in this document is the
proprietary and confidential information of ENPHASE
ENERGY, Inc.. You will not provide, make available
or disclose (or use for any purpose other than that
contemplated by this document) any such information
to any other party without the express, written consent
of ENPHASE ENERGY, Inc.
D
C
SIZE
SHEET OF
REV
DRAWING NO.
2
DWN BY
ENGR
MFG
TITLE
THIRD ANGLE PROJECTION
3D MODEL
REVISIONS
REV DESCRIPTION CHKD DATE
APPROVALS DATE
B
DO NOT SCALE THIS DRAWING
Scale: Full
THE MAXIMUM CURRENT BACKFED BY THIS SYSTEM TO
THE MAIN PANEL MAY BE CONTROLLED ELECTRONICALLY.
REFER TO MANUFACTURER’S INSTRUCTIONS
FOR MORE INFORMATION.
PCS CONTROLLED CURRENT SETTING: AMPS
DATE OF CALCULATION AND SETTING:
130.00
30.00
01
NOTES:
2. BACKGROUND COLOUR: WHITE, CONTENT COLOUR : REFER TABLE. VERIFY THE COLOUR WITH PANTONE SHADE CARD.
3. USE UV RESISTANT INK.
4. COMPLETED LABELS TO BE PACKAGED WITH PART NUMBER AND REVISION, MFG CODE AND DATE.
5. SUBMIT ALL ARTWORK SAMPLES WITH FAIR FOR APPROVAL.
6. LABEL MUST BE UL RECOGNIZED (PGDQ2) AND CSA ACCEPTED AS SUITABLE FOR OUTDOOR USE AT
TEMPERATURES FROM -40°C TO +65°C AND SUITABLE FOR THE SURFACE TO BE APPLIED (PER UL RECOGNIZED
COMPONENT DIRECTORY). EACH LABEL MUST BE MARKED WITH VENDOR’S MARK AS DEFINED IN THE CSA LIST OF
ACCEPTED ADHESIVE-TYPE NAMEPLATES. THE SMALLEST SHIPPING PACKAGE MUST BE MARKED WITH SUPPLIER’S
NAME AND UL DESIGNATION.
7. FINISHED PART MUST BE ROHS COMPLIANT (EU ROHS DIRECTIVE 2015/863/EU). MANUFACTURER WILL BE
REQUIRED TO CERTIFY ROHS COMPLIANCE. IF THERE IS A CONFLICT BETWEEN THE SPECIFICATIONS AND
ROHS COMPLIANCE, THE VENDOR MUST CONTACT ENPHASE FOR CLARIFICATION.
8. ALL DIMENSIONS ARE IN MILLIMETERS.
9. GENERAL TOLERANCE: +/- 0.3mm.
Colour Pantone Colour Code
BRIGHT RED C
01
Colour Table - SEE NOTE 2
HW
1. MATERIAL
FOR SHEET FORM: USE 3M 7908 , MATERIAL THICKNESS: 0.051mm.
GLOSS RADIANT WHITE POLYESTER (0.051mm THICK) WITH #350 ACRYLIC ADHESIVE (0.046mm
THICK) AND 90# BLEACHED KRAFT SHEET (0.170mm THICK).
Section D - Power Control System (PCS)
Recommended area to ax - On the dead front below the transparent breaker, position the cover for the main breaker.