EasyManua.ls Logo

enphase IQ7-B1200-LN-I-INT01-RV0 - Battery LED is Solid Yellow; System Alert: “AC Battery(ies) with Critical Temperature”

enphase IQ7-B1200-LN-I-INT01-RV0
24 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
© 2019 Enphase Energy Inc.
19
Battery LED is Solid Yellow
Check the temperature in the room and increase cooling and/or ventilation as required to meet
temperature requirements. The Battery requires an ambient temperature between -20° C and 45° C,
and where relative humidity is between 5 and 95 percent.
Check that the front, top, and sides of the AC Battery array have at least 300 mm of unobstructed
clearance.
NOTE: If the AC Battery registers a high temperature event, it responds by reducing
operation to correct internal temperature.
System Alert: AC Battery(ies) with Critical Temperature”
Check the temperature in the room and increase cooling and/or ventilation as required to meet
temperature requirements. The AC Battery requires an ambient temperature between -20° C and 45°
C, and where relative humidity is between 5 and 95 percent.
Check that the front, top, and sides of the AC Battery array have at least 300 mm of unobstructed
clearance
.
NOTE: If the AC Battery registers a high temperature event, it responds by reducing
operation to correct internal temperature.