Power for UPS Circuit Breaker Wiring AWG or m
㎡
6000VA 40A 10 AWG or 5.5m
㎡
10000VA 60A 8 AWG or 8 m
㎡
Fig. 2
5.4 Default settings at the factory
On the LCD display you will find several of the UPS parameters to select.
Default settings are as follows:
Settings Selection Factory default
Output Voltage Setting 208/220/230/240 Vac 230V (FOR HV series)
Input/Bypass Voltage
±10%
+10/-15%
+15/-20%
+10/-15%
Input/Frequency
±2%
±5%
±7%
±5%
HE Mode Setting On/Off Off
Free Run Mode On/Off On
Bypass Enable/Disable at free run mode Disable/Enable Disable
Alarm silence On/Off Off
Site wiring alarm Enable/Disable Disable
External Battery pack setting 0, 1, 2 0
You may change default settings, but we recommend that this is done after installation and
before starting up loads. Read UPS configurations in chapter 7.2 for more information.