EasyManua.ls Logo

Enplus EVO UPS 6000VA - System Configuration

Default Icon
40 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
8
activated in the LCD panel, though on-line can be run permanently if preferred.
Free Run Mode
The UPS operates in free run mode when input frequency is outside of the selected input
frequency range. Free run mode is when output frequency does not match input frequency.
When starting the UPS, the frequency regulation detected is 50 or 60 Hz ±0.25Hz. Please
refer to chapter 7.2 if you want bypass available while running in free run mode.
Diagnostic tests
When you start the UPS, a diagnostic test is automatically executed that checks electronics,
battery, and reports any problems on the LCD display.
An advanced battery management system always monitors the conditions of the batteries
sends any forewarnings if replacement is needed. Otherwise every 30 days of normal mode
operation, a battery discharge test is performed and any problems reported on the LCD
display.
Except during the first 24 hours after startup while the UPS is in charging mode (please see
chapter 7.2), diagnostic tests can be performed manually from the front panel at any time.
2.2 System configuration
The UPS device and the internal backup battery make up the system. Depending on the site
and load requirements of the installation, certain additional options are available as a tailored
solution.
Planning a UPS system, the following should be taken into consideration:
The total demand of the protected system shall dictate the output power rating (VA). Allow a
margin for future expansion or calculation inaccuracies from measuring power
requirements.
Backup time needed will indicate the battery size needed. If load is less than the UPS
nominal power rating then actual backup time is longer.
The following options are available:
External Battery Cabinets
Transformer cabinets

Related product manuals