30
UPS Dimensions
W x D x H mm (inch)
W/O ISOTR
428 x 597 x 130
(16.9” x 23.5” x 5.1”)
428 x 658 x 130
(16.9” x 25.9” x 5.1”)
Net Weight
kg (lb) W/O ISOTR
20 (44.0) 24 (52.8)
UPS Shipping Weight
kg (lb) W/O ISOTR
24 (52.8) 28 (61.6)
Environment
Operating Temperature 0~40
°
C / 32~104
°
F
Storage Temperature -20~50
°
C / -4~122
°
F
Altitude 2000 meters max
Audible Noise
(1 meter from surface)
60 dBA < 60 dBA
Relative Humidity 0 ~ 95% humidity, non-condensing
Conformance
Safety CE
EMC (EMS / EMI) EN 62040-2, CISPR 22
EN 62040-2
EN 62040-2, CISPR 11
Equipment Protection
Policy
Warranty policy may vary depends on region
Power Dissipation
1433 BTU/h 2389 BTU/h
WARNING:
"When power supplied by external batteries, output toward loads must be
limited to less than 90% of overall power generation