12
5. Troubleshooting
WARNING
High voltage is inside the inverter, do not open or
disassemble it! Attempting to service the unit yourself
may cause the risk of electrical shock or fire!
Problem
Possible
Cause
Solution
Input LED blink,
fault red LED
slow blink
Input voltage is
too high or too
low
Measure the input
voltage. The inverter
recovers when the input
becomes normal.
Load LED blink,
fault red LED fast
blink
Overload or load
short
Check out if the AC load
is within the rated power
or whether there is load
short.
Fault orange
LED fast blink
Over
temperature
inside the
inverter
Improve the quality of
ventilation and do not
block the vent. Restart
the inverter when it is
cool down.
Fault red LED
Inverter
abnormal
Remove all the
connected plugs then
restart. If inverter works
well, please check the