Operating Instructions
Transponder-Coded Safety Switch CTP/CTA-L1/2-BR
12
(translation of the original operating instructions) 2537376-01-04/21
6.5.2. Switching states on version CTP/CTA-L1/L2 with control via IO-Link communication
Guard closed and locked
Bit CL
UA*
0V
Guard closed and not locked
Bit CL
UA*
0V
Guard open
Bit CL
UA*
0V
(Auxiliary) voltage* at guard locking
solenoid CTP/CTA-L1
on off* on irrelevant
Bit CL 0 irrelevant 1
(Auxiliary) voltage* at guard locking
solenoid CTP/CTA-L2
on on off* irrelevant
Bit CL 1 0 irrelevant
Safety outputs FO1A and FO1B
on off off
Guard locking signal OL on off off
Door position signal OD on on off
* In some product variants the auxiliary voltage UA is connected internally to the operating voltage UB.