13. System status table CTP/CTA-L1/2-BR
Operating mode
Actuator/door position
Safety outputs FO1A and
FO1B
Guard locking signal OL
Door position signal OD
LED indicator
Output
State
STATE (green)
DIA (red) and diag-
nostic signal OI
LOCK (yellow)
Self-test
X off off off 5Hz Self-test after power-up
X off off off 5Hz 1 x No communication with the BR/IO-Link Gateway
Normal operation
closed on on on Normal operation, door closed and locked
closed off on on
1 x in-
verse
Normal operation, door closed and locked, safety outputs
not switched because:
- Preceding device in the switch chain signals door open
(only with series connection)
open off off off 1 x
1 x
Normal operation, door open, ready for guard locking
closed off off on
1 x in-
verse
Normal operation, door closed and not locked
open off off off 1 x Normal operation, door open
Teach-in operation
(only unicode)
open off off off 3 x Device in teach-in standby
closed off X on 1 Hz Teach-in operation
X off X X
Positive acknowledgment after completion of teach-in
operation
Fault display
X off x x 1 x
or
1 x in-
verse
Error in the teach-in operation (only unicode)
Actuator removed from the actuating range prior to the
end of the teach-in operation or faulty actuator detected
X off off off 2 x
Input fault
(e.g. missing test pulses, illogical switch state from
previous switch in the switch chain)
X off off off 3 x
Read error
(e.g. actuator faulty)
X off off off 4 x
Output fault
(e.g. short circuit, loss of switching ability)
X off X X 5 x Disabled actuator detected/environment error
X off off off Internal fault/plausibility error
Key to symbols
LED not illuminated
LED illuminated
1 x in-
verse
LED illuminated, briey goes off 1 x
5Hz
LED ashes at 5Hz
3 x
LED ashes three times, and this is then repeated
LEDs ash alternately
X Any state
When DIA ashes inversely once, the fault display can generally be reset by opening and closing the guard after remedying
the cause. If the fault is still displayed afterward, as well as for all other fault displays, briey interrupt the power supply.
Contact the manufacturer if the fault display is not reset after restarting.
Important!
If you do not nd the displayed device status in the system status table, this indicates an internal device
fault. In this case, contact the manufacturer.