Operating Instructions
Transponder-Coded Safety Switch CTP/CTA-L1/2-BR
20
(translation of the original operating instructions) 2537376-01-04/21
10.4. Requirements for connecting cables
CAUTION
Risk of damage to equipment or malfunctions as a result of incorrect connecting cables.
Ì Use connection components and connecting cables from EUCHNER.
Ì On the use of other connection components, the requirements in the following table apply.
EUCHNER provides no warranty for safe function in case of failure to comply with these require-
ments.
Observe the following requirements with respect to the connecting cables:
For safety switches CTP/CTA-…-BR-…-SAB-… with plug connectors 2 x M12
Parameter Value Unit
Conductor cross-section, min. 0.25 mm²
R max. 60 W/km
C max. 120 nF/km
L max. 0.65 mH/km
Recommended cable type LIYY 8 x 0.25mm² or 5 x 0.34mm²
For safety switches CTP/CTA-…-BR-…-SA-… with plug connector M12, 8-pin
Parameter Value Unit
Conductor cross-section, min. 0.25 mm²
R max. 60 W/km
C max. 120 nF/km
L max. 0.65 mH/km
Recommended cable type
LIYY 8 x 0.25 mm²
For safety switches CTP/CTA-…-BR-…-SH-… with plug connector M23 (RC18)
Parameter Value Unit
Conductor cross-section, min. 0.25 mm²
R max. 60 W/km
C max. 120 nF/km
L max. 0.65 mH/km
Recommended cable type
LIYY 8 x 0.25 mm²