23
112657-12-01/15 (translation of the original operating instructions)
Operating Instructions Safety Systems
MGB-L0…-AR.-… and MGB-L0…-AP.-…
EN
11.4. Requirements for connection cables
CAUTION
Risk of damage to equipment or malfunctions as a result of incorrect connection cables.
Ì On the usage of other connection components, the requirements in the following table apply. EU-
CHNER provides no warranty for safe function in case of failure to comply with these requirements.
Observe the following requirements with respect to the connection cables:
Parameter Value Unit
Conductor cross-section min. 0.13 mm²
R max. 60
Ω/km
C max. 120 nF/km
L max. 0.65 mH/km
11.5. Notes on cable laying
Lay all MGB connection cables in a common cable harness.
PLC
+ 24 V DC
cabinet
0 V
MGB-L.-...
FI1A/
FI1B
FO1A/
FO1B
UB 0V UA 0V
Important: lay cables in a common harness
Figure 14: Stipulated cable laying