NTC analog inputs (10K @ 25 °C, 77 °F)
Kind of sensor: β3435.
Working range: from -50 to 120 °C (-58 to 248 °F).
Accuracy: ±0.5% of the full scale between -40 and 100 °C, ±1 °C
between -50 to -40 °C and between 100 and 120 °C .
Resolution: 0.1 °C.
Conversion time: 100 ms.
Protection: no protection.
NTC analog inputs (10K @ 25 °C, 77 °F)
Kind of sensor: NTC 2.
Working range: from -40 to 86 °C (-40 to 186 °F).
Accuracy: ±1 °C.
Resolution: 0.1 °C.
Conversion time: 100 ms.
Protection: no protection.
NTC analog inputs (10K @ 25 °C, 77 °F)
Kind of sensor: NTC 3.
Working range: from -40 to 86 °C (-40 to 186 °F).
Accuracy: ±1 °C.
Resolution: 0.1 °C.
Conversion time: 100 ms.
Protection: no protection.
Pt 1000 analog inputs (1K @ 0 °C, 32 °F)
Working range: from -100 to 400 °C (-148 to 752 °F ).
Accuracy: ±0.5% of the full scale between -100 and 200 °C, ±2 °C
between 200 to 400 °C.
Resolution: 0.1 °C.
Conversion time: 100 ms.
Protection: no protection.
0-20 mA / 4-20 mA analog inputs
Input resistance: to 200 .
Accuracy: ±0.5% of the full scale.
Resolution: 0.01 mA.
Conversion time: 100 ms.
Protection: no protection; the maximum current allowed on each input is
25 mA.
0-5 V ratiometric / 0-10 V analog inputs
Input resistance: to 10K .
Accuracy: ±0.5% of the full scale.
Resolution: 0.01 V.
Conversion time: 100 ms.
Protection: against the reversal of the polarity.