Evco S.p.A. EVF815 | Installer manual ver. 1.1 | Code 144F815E114
page 32 of 58
r17 0.0 99.0 °C/°F (1) 5.0
"temperature detected by the needle probe - cabinet
temperature" minimum difference such to consider the first
phase of the test to verify correct insertion of the needle
probe completed successfully (consider the difference
without sign)
0.0 = the test will not be performed (neither first or second
phase)
r18 1 99 s 60
duration of the second phase of the test for verification of
correct insertion of the needle probe
r19 0 1 - - - - 0
quick modification value during the "On" status before
starting the operating cycle
0 = work set-point during blast chilling or during deep
freezing
1 = blast chilling or deep freezing end temperature
r20 0 1 - - - - 1
memorisation of the quick modification value during the
"On" status before starting the operating cycle
0 = no (on start-up of the successive same cycle, the
values established with parameters r7 and r3 or
those establishes with r4 and r8 will be re-proposed)
1 = yes (on start-up of the successive same cycle the
rapidly modified values will be re-proposed before
starting the previous same cycle)
Par. Min. Max. Unit Default Compressor protections
C0 0 240 min 0
minimum time between restoring the power supply after a
power cut, occurring during an operating cycle and
compressor switch-on
C1 0 240 min 5
minimum time between two consecutive compressor switch-
ons (3)
C2 0 240 min 3
minimum time between compressor switch-off and
successive switch-on (3)
C3 0 240 s 0 compressor switch-on minimum duration
C4 0 240 min 10
duration of compressor switch-off during the cabinet probe
error (“Pr1” code) that occurs during storage; see also
parameter C5