Evco S.p.A. EVF815 | Installer manual ver. 1.1 | Code 144F815E114
page 35 of 58
A10 0 240 min 5
duration of a power cut such to cause the power cut alarm
to be memorised ( “PF” code)when the power is supplied
0 = the alarm will not be signalled
AA 0 240 s 5
duration of buzzer activation on conclusion of blast chilling
and deep freezing
A11 0,1 15,0 °C/°F (1) 2,0 parameters A1 and A4 differential
A13 0 1 - - - - 1
memorisation of the temperature-controlled blast chilling or
temperature-controlled deep freezing non concluded within
maximum duration alarm (“tiME”)
1 = yes
Par. Min. Max. Unit Default Evaporator and condenser fan
F0 0 2 - - - - 1
evaporator fan activity during pre-cooling, blast chilling and
deep freezing
0 = off
1 = on; see also parameters F16 and F17
2 = parallel to the compressor; see also parameters F9
and F17
F1 -99.0 99.0 °C/°F (1) -1.0
evaporator temperature above which the evaporator fan is
off during storage (only if parameter F2 is set at 3); see
also parameter F8(10)
F2 0 3 - - - - 3
evaporator fan activity during storage
0 = off
1 = on
2 = parallel to the compressor; see also parameter F9
3 = on; see also parameter F1
F3 0 15 min 2
duration of evaporator fan standstill (the compressor can be
on during evaporator fan standstill, the defrosting output
will remain deactivated and the evaporator fan will remain
off)
F8 0.1 15.0 °C/°F (1) 2.0 F1, F16 and F17 parameters differential
F9 0 240 s 0
evaporator fan switch-off delay from compressor switch off
(only if parameter F0 and/or parameter F2 are set at 2)