Evco S.p.A. EVF815 | Installer manual ver. 1.1 | Code 144F815E114
page 34 of 58
d5 0 99 min 30
defrosting delay on start-up of storing
0 = defrosting will be started on expiry of the time
established with parameter d0
d7 0 15 min 2
dripping duration (the compressor and the evaporator fan
remain off during dripping and the defrosting output will be
deactivated)
d15 0 99 min 0
minimum duration of compressor switch-on on activation of
defrosting so these can be activated (only if parameter d1 is
set at 1) (7)
d16 0 99 min 0
duration of pre-dripping (only if parameter d1 is set at 1;
the compressor and evaporator fan will be off during pre-
dripping and the defrosting output will remain activated)
Par. Min. Max. Unit Default Temperature alarms (8) (9)
A1 0.0 99.0 °C/°F (1) 10.0
cabinet temperature below which the minimum temperature
alarm is activated (relative to the work set-point, i.e. “r10 -
A1” during post blast chilling storage and “r11 - A1” during
post deep freezing storage; (AL” code); see also
parameter A11 (4)
A2 0 1 - - - - 1
enabling of minimum temperature alarm (“AL” code)
1 = yes
A4 0.0 99.0 °C/°F (1) 10.0
cabinet temperature above which the maximum
temperature alarm is activated (relative to the work set-
point, i.e. “r10 +A4” during post blast chilling storage and
“r11 +A4” during post deep freezing storage; (“AH” code);
see also parameter A11 (4)
A5 0 1 - - - - 1
enabling of maximum temperature alarm (“AH” code)
1 = yes
A7 0 240 min 15 temperature alarm delay(“AL” code and “AH” code)
A8 0 240 min 15
maximum temperature alarm delay (“AH” code) from the
conclusion of evaporator fan stop and storage start-up