EVCO S.p.A.
EV3 MVC & EVD MVC | Application manual ver. 1.0 | Code 144EV3MVI104
page 58 of 72
3 = Humidity
4 = Free cooling/heating
5 = OFF
6 = External air limitation
S11 % Mixing chamber damper aperture RO
S12
Recovery heat exchanger function mode
0 = Disabled
1 = OFF
2 = ON
RO
S13
Recovery heat exchanger defrost phase
0 = Not in defrost
3 = Defrosting
5 = Dripping
RO
S14 0 100 %rH Humidity regulation setpoint RW
S15
Function mode
0 = Cooling
1 = Heating
2 = Auto+Cooling
3 = Auto+Heating
RO
S16 0 2
Set function mode
0 = Cooling
1 = Heating
2 = Auto
RW
S17 Change-over probe value RO
S18 -50,0 90,0 °C Temperature regulation setting RW
S19
Temperature regulation mode
0 = Disabled
1 = Follow-on regulation
2 = Room temperature setpoint
3 = Supply setpoint
4 = Digital input
RO
S20 °C
Regulation probe value
-3276.8 = ERR
RO
S21 °C Temperature regulation setpoint RO
S22
1st coil type
0 = Not available
1 = Thermodynamic
2 = 3-point, water
3 = Modulating, water
4 = ON-OFF, water
5 = 2-step, electric
6 = Modulating, electric
7 = ON-OFF, electric
8 = Not configured
RO
S23
2nd coil type
0 = Not available
2 = 3-point, water
3 = Modulating, water
4 = ON-OFF, water
RO