EV3 MVC & EVD MVC | Application manual ver. 1.0 | Code 144EV3MVI104
page 59 of 72
5 = 2-step, electric
6 = Modulating, electric
7 = ON-OFF, electric
8 = Not configured
S24
Thermodynamic coil function mode
0 = OFF
1 = ON
RO
S25
Water coil function mode
0 = OFF
1 = ON
RO
S26 % Valve opening RO
S27
Electric coil function mode
0 = OFF
1 = Step 1
2 = Step 2
RO
S28 Electric coil percentage RO
S29 Steps in operation RO
S30
Defrost phase
0 = Not in defrost
1 = Awaiting defrost 1 input
2 = Awaiting defrost 2 input
3 = Defrosting
4 = Awaiting defrost input
5 = Pre-drip
6 = Dripping
RO
S31 S Defrost time RO
S32 M Delay between defrosts RO
S33 10S Safety time RO
S34
Compressor in alarm mode
0 = OFF
1 = ON
RO
S35 0 0 H Compressor operating hours RW
S36 0 0 H Fan operating hours RW
S37 0 0 H Unit operating hours RW
S38 Expansion resources used RO
S39 E2 write request status RO
S40 °C
Room probe value
-3276.4 = Disabled
-3276.8 = ERR
RO
S41 °C
Supply probe value
-3276.4 = Disabled
-3276.8 = ERR
RO
S42 °C
External probe value
-3276.4 = Disabled
-3276.8 = ERR
RO
S43 °C Expulsion probe value RO