EVCO S.p.A.
EV3 MVC & EVD MVC | Application manual ver. 1.0 | Code 144EV3MVI104
page 60 of 72
-3276.4 = Disabled
-3276.8 = ERR
S44 °C
Water probe value
-3276.4 = Disabled
-3276.8 = ERR
RO
S45 °C
Compressor defrost probe value
-3276.4 = Disabled
-3276.8 = ERR
RO
S46 °C
Compressor discharge temperature probe value
-3276.4 = Disabled
-3276.8 = ERR
RO
S47 %rH
Return air humidity probe value
-3276.4 = Disabled
-3276.8 = ERR
RO
S48 PPM
CO
2
probe value
-3276.4 = Disabled
-3276.8 = ERR
RO
S49 %
Remote control probe value
-3276.4 = Disabled
-3276.8 = ERR
RO
S50
Pressure differential control probe value
-3276.4 = Disabled
-3276.8 = ERR
RO
S51 Hz
Tachometric supply digital input value
-1 = Disabled
RO
S52 Hz
Tachometric return digital input value
-1 = Disabled
RO
S53
Supply fan thermal switch digital input value
-1 = Disabled
0 = OFF
1 = ON
RO
S54
Return fan thermal switch digital input value
-1 = Disabled
0 = OFF
1 = ON
RO
S55
Supply flow switch digital input value
-1 = Disabled
0 = OFF
1 = ON
RO
S56
Return flow switch digital input value
-1 = Disabled
0 = OFF
1 = ON
RO
S57
High pressure digital input value
-1 = Disabled
0 = OFF
1 = ON
RO
S58 Low pressure digital input value RO