EVO/ECM-Modbus RTU Series 2 Page 9
Application Guide
©2020 All Rights Reserved
Evolution Controls Inc.
San Diego, CA USA
Default Registers
Registers 10 through 14 contain default operating data. The EVO/ECM-Modbus RTU stores this
data in non-volatile E
2
PROM, so the data is available when the RTU is powered up. Default values
are copied to their respective dynamic registers on RTU power up, on RTU reset, or when a
communications timeout occurs.
Configuration Registers
Registers 15 through 18 store EVO/ECM-Modbus RTU configuration information in non-volatile
E
2
PROM.
RPM Alarm Limit Registers
Registers 19 through 26 store high and low alarm limits for each motor. These values are stored in
E
2
PROM only. There are no associated dynamic registers for RPM limits.