5.2 DIP SWITCH SETTINGS DS1 SW1,SW2,SW3 : OPERATING LOGIC
OPERATING LOGIC
DS 1 : SW 1 - SW 2 - SW 3
LOGIC SW 1 SW 2 SW 3
PAUSE
TIME
DESCRIPTION
E (default)
Semiautomatic
OFF OFF OFF NO
One command opens, the next one closes
A
Automatic
ON ON ON
0 - 4
min
One command opens, waits for the pause time an then
closes automatically
S
Security
OFF OFF ON
0-4
min
One command opens, waits for the pause time and
then closes automatically. If the closing safety is acti-
vated or another command is given during the pause
time it closes
EP
Semiautomatic
step by step
OFF ON OFF NO
One command opens, the next one closes. During the
movement a command stops the gate
AP
Automatic
step by step
OFF ON ON
0-4
min
One command opens, waits for the pause time and
then closes automatically. A command during the
pause time holds the gate open
SP
Security
step by step
ON OFF OFF
0-4
min
One command opens, waits for the pause time and
then closes automatically. If the closing safety is activa-
ted during pause time the gate closes in 5 s. A com-
mand during pause time holds open the gate
B
Manned Pulsed
ON OFF ON NO
An open A command opens the gate, an open B com-
mand closes the gate
C
Manned Constant
ON ON OFF NO
Holding open A active opens the gate, holding Open B
active closes the gate
For more details on the operating logics please refer to Chapter XX