6.6 FINAL CHECKS
1. Carry out a complete functional test of the automa-
tion and all the installed devices.
2. Make sure that the forces generated by the leaf are
within the limits permitted by the current regula-
tions. Use an impact force tester in accordance
with standard EN 12453. For non-EU countries,
if there are no specific local regulations, the static
force must be less than 150 N. If necessary, adjust
the anti-crushing system and make any other ad-
justments that may be necessary, also by referring
to the actuator instructions.
Refer to the actuator instructions for any additional
tests that may be required.
6.7 CLOSE THE ENCLOSURE
Close the enclosure using the screws on the cover.
Close the enclosure