FältCom ECII Flex - Alarm Testing and Delay; Alarm Receiver Testing and Delay Settings

FältCom ECII Flex
40 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
1. Alarm Receiver 1
2. Alarm Receiver 2
3. Sequence Receiver 3
4. Sequence Receiver 4
5. Sequence Receiver 5
6. Sequence Receiver 6
7. Test alarm/Routine call receiver
8. Technical alarm receiver
9. Information alarm receiver
Change of time delay for alarm button
The delay time on the alarm button can be set to between 1 and 30 seconds. The default time
is 5 seconds.
From keypad:
< 1-30 >
From phone:
053 < 130 > #
Note: The delay programmed is the time until the alarm is activated by the ECII™ Flex. It will
take an additional two seconds before the alarm is called out because of the start-up time and
latency in the PSTN.
Connections to telephone line with automatic dial/
connection.
If the ECII™ Flex is connected to a telephone line with automatic dial or automatic connection;
where the telephone exchange directs the call without the user entering any keys, a pause must
be added to prevent the ECII™ Flex from calling out. One
– symbol represents a pause of
two seconds. There is no need to program any telephone number since the telephone exchange
takes care of that.
From keypad:
From phone:
001 #
Automatic test alarm/routine call
This function calls a test alarm/routine call receiver to verify the connection between the
ECII™ Flex and the alarm receiver. Automatic test alarm/routine call shall only be pro-
grammed if the ECII™ Flex is connected to an alarm central, the alarm central can verify that
the incoming test alarms/routine calls are correct. A test alarm/routine call is silent; no tones
are heard in the lift.
When the test alarm/routine call function is activated the first test alarm/routine call is sent 5
minutes after exiting programming mode and the following test alarm/routine call is sent 10
hours after the first. The third and following test alarm/routine call are sent every N x 24 hours
where N is the test alarm/routine call interval in days. Note that the automatic test counter is
reset every time an automatic test related parameter is changed and when the power is dis-
connected from the ECII™ Flex. If the ECII™ Flex has been out of power and the power re-
turns it will send the next test alarm/routine call after 10 hours.
If a test alarm/routine call fails the next attempt is made after 10 minutes. In total 10 attempts
are made. If a test alarm/routine call is received for instance in the third attempt the next test
alarm/routine call will be sent N x 24 hours after the last successful attempt. This means that
the ECII™ Flex automatically distributes the test alarms/routine calls to a time when the tele-
phone line of the alarm receiver is normally available.